Name:CH6 Digital Indicator

1.The Intrinsic Error is less than 0.5%F.S


2.It is adaptable to such signals as voltage, current, RTD, T/C, etc.


3.2-point alarm output is available


4.Re-Transmitted Output can provide other devices with the displaying value in the form of standard current or voltage output. The displaying value is measured and transformed by the instrument.

Description

CH6 Series Single Input Channel Intelligent Digital Indicators can be used with variety of analog output sensors and transmitters to accomplish the measurement, transfer, display, transmission, recording and control of temperature, pressure, level, component, force and displacement, etc.

Models Numbers

                1     2  3   4        5        6     7 
CH6 / oo  R  T  A o B   o
Ø 1Dimensions W×H×L
A160×80×125 or 80×160×125
B96×96×76
C96×48×82 or 48×96×82
D72×72×75
E48×48×108
Ø 2Faceplate Types HHorizontal Type
                 S
Vertical Type
                 F
Square Type
Ø 3Display Types
RMeasured ValueRed
Ø 4The Number of Alarm Outputs
T2 Alarm Outputs
Ø 5Re-Transmitted Output
A0No Output
A1DC Current Output4 mA ~20 mA,0 mA ~10 mAor0 mA ~20 mA
A2DC Voltage Output0 V ~5 V, 1 V ~5 V
Ø 6Power Supply Output
B0No
B124V DC
B212V DC
Ø 7Input Signal
EThermocouple or Radiation Thermometer
RRTD or Resistance
I DC Current
VDC Voltage
 3 Specifications
Ø          Power Supply85V~220VAC, 100VDC~380VDC, power      consumption less than 4VA.
Ø   Operating Conditions0~50,Humidity less than 85%R.H.
Ø        Display range-1999~9999the position of the decimal point can be     set.
Ø               Types of the input signal
Voltage1V~5V DC or 0V~5V DC is selectable by settings.
Current4mA~20mA, 0mA~10mA or 0mA~20mA is selectable by settings.
RTDPt100Cu100Cu50BA1, BA2 or G53 is selectable by settings.
ThermocoupleK, S, R, B, N, E, J, T is selectable by settings.
Input signal type
Display Range
Input signal type
Display Range
Voltage
0~5VDC
-1999~9999
 
 
 
 
 
Thermocouple
K
-100~1300
1~5VDC
S
0~1700
0~10VDC
R
0~1700
Current
4~20mA
-1999~9999
B
500~1800
0~10mA
E
-100~800
0~20mA
J
-100~1100
RTD
Pt100
-200.0~500.0
T
-100~400
Cu100
-50.0~150.0
 
 
Cu50
-50.0~150.0
 
 
BA1
-200.0~650.0
 
 
BA2
-200.0~500.0
 
 
G53
-50.0~150.0
 
 
 
Ø Intrinsic ErrorLess than±0.5%F.S
Ø Periods of measurement and control0.2 seconds
Alarm Output : 2Alarm Outputs, Contact capability 220V AC, 3A
Ø Re-Transmitted Output
·        Photo-isolation
·        4mA~20mA, 0mA~10mA or 0mA~20mA DC current output, is selectable by settings. Load capability more than 600Ω
·        1V~5V, 0V~5V or 0V~10V DC voltage output, remark on order.
·        Resolution of output1/1000, error less than ±0.5% F.S 
Ø Power Supply output
? Universal Power SupplyUsed for supplying power to Transmitter, the error of output value from nominal value is less than ±5%, load capacity is more than 50mA.
? For 24V DC, 12V DC, 5V DC or other specifications, notification is needed on order.