Name:CH6 Digital Indicator
1.The Intrinsic Error is less than 0.5%F.S
2.It is adaptable to such signals as voltage, current, RTD, T/C, etc.
3.2-point alarm output is available
4.Re-Transmitted Output can provide other devices with the displaying value in the form of standard current or voltage output. The displaying value is measured and transformed by the instrument.
Description
CH6 Series Single Input Channel Intelligent Digital Indicators can be used with variety of analog output sensors and transmitters to accomplish the measurement, transfer, display, transmission, recording and control of temperature, pressure, level, component, force and displacement, etc.
Models Numbers
1 2 3 4 5 6 7
CH6 / o—o R T A o B o o
Ø 1:Dimensions (W×H×L)
A:160×80×125 or 80×160×125
B:96×96×76
C:96×48×82 or 48×96×82
D:72×72×75
E:48×48×108
Ø 2:Faceplate Types H:Horizontal Type
S:Vertical Type
F:Square Type
S:Vertical Type
F:Square Type
Ø 3:Display Types:
R:Measured Value(Red)
Ø 4:The Number of Alarm Outputs
T:2 Alarm Outputs
Ø 5:Re-Transmitted Output
A0:No Output
A1:DC Current Output(4 mA ~20 mA),(0 mA ~10 mA)or(0 mA ~20 mA)
A2:DC Voltage Output(0 V ~5 V), (1 V ~5 V)
Ø 6:Power Supply Output
B0:No
B1:24V DC
B2:12V DC
Ø 7:Input Signal
E:Thermocouple or Radiation Thermometer
R:RTD or Resistance
I: DC Current
V:DC Voltage
3 Specifications
Ø Power Supply:85V~220VAC, 100VDC~380VDC, power consumption less than 4VA.
Ø Operating Conditions:0℃~50℃,Humidity less than 85%R.H.
Ø Display range:-1999~9999,the position of the decimal point can be set.
Ø Types of the input signal:
Voltage:1V~5V DC or 0V~5V DC is selectable by settings.
Current:4mA~20mA, 0mA~10mA or 0mA~20mA is selectable by settings.
RTD:Pt100,Cu100,Cu50,BA1, BA2 or G53 is selectable by settings.
Thermocouple:K, S, R, B, N, E, J, T is selectable by settings.
Input signal type
|
Display Range
|
Input signal type
|
Display Range
|
||
Voltage
|
0~5VDC
|
-1999~9999
|
Thermocouple
|
K
|
-100~1300℃
|
1~5VDC
|
S
|
0~1700℃
|
|||
0~10VDC
|
R
|
0~1700℃
|
|||
Current
|
4~20mA
|
-1999~9999
|
B
|
500~1800℃
|
|
0~10mA
|
E
|
-100~800℃
|
|||
0~20mA
|
J
|
-100~1100℃
|
|||
RTD
|
Pt100
|
-200.0~500.0℃
|
T
|
-100~400℃
|
|
Cu100
|
-50.0~150.0℃
|
|
|
||
Cu50
|
-50.0~150.0℃
|
|
|
||
BA1
|
-200.0~650.0℃
|
|
|
||
BA2
|
-200.0~500.0℃
|
|
|
||
G53
|
-50.0~150.0℃
|
|
|
Ø Intrinsic Error:Less than±0.5%F.S
Ø Periods of measurement and control:0.2 seconds
Alarm Output : 2Alarm Outputs, Contact capability 220V AC, 3A
Ø Re-Transmitted Output
· Photo-isolation
· 4mA~20mA, 0mA~10mA or 0mA~20mA DC current output, is selectable by settings. Load capability more than 600Ω
· 1V~5V, 0V~5V or 0V~10V DC voltage output, remark on order.
· Resolution of output:1/1000, error less than ±0.5% F.S
Ø Power Supply output
? Universal Power Supply:Used for supplying power to Transmitter, the error of output value from nominal value is less than ±5%, load capacity is more than 50mA.
? For 24V DC, 12V DC, 5V DC or other specifications, notification is needed on order.